Series 651mHNK

Good to know Data & facts

Connection size

DN 15 to DN 50 1/2" to 2"

Set pressure

2.5 bar and 3 bar

Temperature

-10 °C to 120 °C
Product design

angle-type

Material

Gunmetal

Nominal width

DN 15 to DN 50
1/2" to 2"

Medium
  • Hot water
Temperature in °C

-10 °C to 120 °C

Pressure in bar

2.5 bar and 3 bar

For the protection of:

  • closed circuit water heaters for drinking water and process water

according to TRD 721, DIN 4753 and DIN 1988 for temperatures up to max. 95°C.

The safety valve is installed in the cold water inlet of the hot water heater according to DIN 1988.


connection types

  • Internal pipe thread
  • CHP units (combined heat and power plants)
  • closed, thermostatically protected water heating systems with flow temperatures up to 120°C and a permissible heat output up to max. 2,700 kW according to TRD 721, DIN 4751 and DIN EN 12828


In the event of failure of the thermostatic control and limiting devices, the safety valve must blow off the entire heating output of the boiler in the form of hot water and steam. Due to the all-metal design, these safety valves can also be used at high ambient or radiant temperatures.

Safety valves are permanently set and lead-sealed at the factory.

TUV-Germany

Approvals

TÜV.SV.21 516:

Usage

Heating (H)

EU type examination

Approvals

01 202 642B-22 T009 TÜV SV 516:

Usage

Heating (H)

Eurasian Conformity

Approvals

RU CDE.CN28.B.00821/20:

:

Usage

Heating (H)

Bureau Veritas

Approvals

26401/C0 BV:

Usage

Heating (H)

Registro Italiano Navale

Approvals

MAC096822XG:

Usage

Heating (H)